Galleon II 1K-3KVA

Galleon II 1K-3KVA

产品概述:PF0.9 online UPSGalleon II 1KVA-3KVA can provide high output power factor up to 0.9 and provide higher performance and efficiency for critical applications. It'···

产品简介

PF0.9 online UPS

Galleon II 1KVA-3KVA can provide high output power factor up to 0.9, and provide higher performance and efficiency for critical applications. It's the same Galleon series with adjustable power management outlets that extend available battery time to critical devices by turning off unnecessary devices. This Galleon II 1KVA-3KVA series is also suitable for loads in laser printers and ultrasonic systems.

main feature

●1KVA/1.5KVA/2KVA/3KVA online UPS system

●Real double conversion online UPS system

● Wide input voltage range (110-300 VAC, 55-150 VAC)

●Input power correction factor 0.99

●Output power factor 0.9

●50/60Hz frequency conversion mode

●Adjustable power management socket

●Emergency power off function (EPO)

●ECO energy saving operation function

●High surge immunity, up to 7KVA, 13KVA, 1300J

●Optional matching generator

●High anti-overload capability and efficient short-circuit protection

●Multiple communication ports such as SNMP/USB/RS-232

●3-section intelligent charging design

●Maximum 8A extended parallel control can be used for long-running models

●Selectable output voltage: 200-240VAC, 100-127VAC

 Applicable to the load of laser printers and ultrasonic systems

      Product Specifications

MODELGalleon II 1K (L)Galleon II 1.5K (L)Galleon II 2K (L)Galleon II 3K (L)
capacity1000VA / 900W1500VA / 1350W2000VA / 1800W3000VA / 2700W
phaseSingle phase with ground
ENTER
voltage range55-150 VAC ± 5 % or 110-300 VAC ± 5 % at 50% load; 80-150 VAC ± 5 % or 160-300 VAC ± 5 % at 100% load
Rated voltage100/110/115/120/127VAC or 200/208/220/230/240VAC
Frequency Range40Hz~70Hz
power factor≧ 0.99 @ Nominal Voltage (100% load)
Harmonic Distortion (THDi)≦ 5% @100~130VAC or 205-245VAC; THDU < 1.6% @ input and full linear load condition with battery fully charged
OUTPUT
The output voltage100/110/115/120/127VAC or 200/208/220/230/240VAC
AC Voltage Regulation (Voltage Mode)± 1%
Frequency Range (Battery Mode)50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz
transfer timeAC mode is battery modeZero
transfer timeInverter to Bypass4 ms (Typical)
Waveform (Battery Mode)Pure Sine Wave
Current crest ratio3:1
Harmonic Distortion≦ 2% THD (Linear Load); ≦ 4% THD (Non-linear Load)
Frequency range (sync range)47~53Hz or 57~63Hz
EFFICIENCY
battery mode89%90%
ECO mode97%
Communication mode90%91%
BATTERY
long extension machineModule charging voltage41.0 VDC ± 1%82.1 VDC ± 1%82.1 VDC ± 1% ,109.6 VDC ± 1%
long extension machineModule charging current (max)1A/2A/4A/6A/8A (Selectable)
long extension machinenumber of modules366,8
long extension machineModular battery typeDepending on the capacity of external batteries
Standard machineCharger voltage41.0 VDC ± 1%82.1 VDC ± 1%82.1 VDC ± 1%, 109.6 VDC ± 1%
Standard machineCharge current (max)1.5A1.5A, 1.2A
Standard machineTypical charging time4 hours recover to 90% capacity
Standard machinequantity366, 8
Standard machineBattery Type12V / 7Ah12V / 9Ah12V / 7Ah12V/9Ah, 12V/7Ah
INDEX
LCD panelUPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions
ALARM
battery modeSounding every 5 seconds
low powerSounding every 2 seconds
overloadSounding every second
FaultContinuously sounding
SURROUNDINGS
Working humidity20~95% RH @ 0- 40°C (non-condensing)
noise levelLess than 50dB @ 1 Meter
PHYSICS
Standard machineNet weight/kg1213.822.526.6, 32.2
Standard machineDimensions, D X W X H (mm)397 X 145 X 220421 X 190 X 318
long extension machineNet weight/kg6.36.510.511.7
long extension machineDimensions, D X W X H (mm)397 X 145 X 220421 X 190 X 318
MANAGE
Optional SNMPPower management from SNMP manager and web browser
Smart RS-232/USBSupports Windows® 2000/2003/XP/Vista/2008, Windows® 7/8/10, Linux, and MAC


Excel Energy Co., Ltd.

0577-62789660

(联系电话 7×24)