With a true double-conversion design, the Galleon series provides powerful and comprehensive protection for your delicate equipment. It can accept a wider input voltage and is suitable for harsh power supply environments. It provides the perfect protection for your precious servers and high-performance workstations. Can be sold to the North American market.

main feature

1KVA/1.5KVA/2KVA/3KVA/6KVA/10KVA online UPS system

●Real double conversion online UPS system

●Excellent microprocessor controller ensures high reliability

●Output power factor 1.0

●Input power correction

●Wide input voltage range (110V-300V)

●Wide input voltage range

●ECO energy saving operation function

●Emergency power off function (EPO)

●Built-in MOV overvoltage cut-off protection and surge immunity, which can realize full-time equipment protection

●Charger with capacity up to 1000W with extremely low ripple current when charging

●Low input current harmonics to reduce power system pollution

●The charging current can be directly adjusted through the LCD panel

●Intelligent battery charger design optimizes battery performance

●Compatible with engine input

●Optional external SNMP slot

       Product Specifications

MODELGalleon II RM 1KGalleon II RM 1.5KGalleon II RM 2KGalleon II RM 3K
capacity1000 VA / 900 W1500 VA / 1350 W2000 VA / 1800 W3000 VA / 2700 W
phaseSingle phase with ground
ENTER
voltage range55-150 VAC ± 5 % or 110-300 VAC ± 5 % at 50% load; 80-150 VAC ± 5 % or 160-300 VAC ± 5 % at 100% load
Rated voltage100*/110*/115*/120/127 VAC or 200/208/220/230/240 VAC
Frequency Range40Hz~70Hz
power factor≧ 0.99 @ Nominal Voltage (100% load)
Harmonic Distortion (THDi)≦ 5% @ nominal input voltage
OUTPUT
The output voltage100*/110*/115*/120/127 VAC or 200/208/220/230/240 VAC
AC Voltage Regulation (Voltage Mode)± 1%
Frequency Range (Battery Mode)50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz
transfer timeAC mode is battery modeZero
transfer timeInverter to Bypass4 ms (Typical)
Waveform (Battery Mode)Pure Sine Wave
Current crest ratio3:1 (max.)
Harmonic Distortion≦ 2% THD (Linear Load); ≦ 4% THD (Non-linear load)
Frequency range (sync range)57~63 Hz or 47~53 Hz
EFFICIENCY
battery mode88%,89%89%88%, 89%90%
ECO mode97%
Communication mode90%91%
BATTERY
long extension machineModule charging voltage27.4 VDC ± 1%, 41.1 VDC ± 1%41.1 VDC ± 1%54.8 VDC ± 1%, 82.1 VDC ± 1%82.1 VDC ± 1%
long extension machineModule charging current (max)1A / 2A / 4A / 8A (Selectable via LCD Setting)
long extension machinenumber of modules2,334.66
long extension machineModular battery typeDepending on the capacity of external batteries
Standard machineCharger voltage27.4 VDC ± 1%41.1 VDC ± 1%54.8 VDC ± 1%, 82.1 VDC ± 1%82.1 VDC ± 1%
Standard machineCharge current (max)1.5 A
Standard machineTypical charging time4 hours recover to 90% capacity
Standard machinequantity2,334, 66
Standard machineBattery Type12 V / 9 AH, 12 V / 7 AH12 V / 9 AH12 V / 9 AH, 12 V / 7 AH12 V / 9 AH
INDEX
LCD MonitorUPS Status, Load level, Battery leve, Battery mode, Input/Output voltage, Discharge timer, and Fault indicators
ALARM
battery modeSounding every 5 seconds
low powerSounding every 2 seconds
overloadSounding every second
FaultContinuously sounding
SURROUNDINGS
Working humidity20~90% RH @ 0- 40°C (non-condensing)
noise levelLess than 50dB @ 1 Meter
PHYSICS
Standard machineNet weight/kg11.6, 14.214.519.5, 26.927.4
Standard machineDimensions, D X W X H (mm)410 x 438 x 88510 x 438 x 88, 630 x 438 x 88630 x 438 x 88
long extension machineNet weight/kg6.46.510.5
long extension machineDimensions, D X W X H (mm)410 x 438 x 88510 x 438 x 88
MANAGE
Optional SNMPPower management from SNMP manager and web browser
Smart RS-232/USBSupports Windows 2000/2003/XP/Vista/2008, Windows 7/8/10, Linux, and MAC