产品概述:DSP technology application Galleon X9 online series passed UL certification. With an output power factor of 0.9 from 1KVA to 10KVA, its transformerless design p···
DSP technology application
Galleon X9 online series is UL listed. With an output power factor of 0.9 from 1KVA to 10KVA, its transformerless design provides a compact footprint in a rack/tower convertible design for easy installation.
main feature
● true double conversion
●DSP technology ensures high performance
●Output power factor 0.9
●Rack/tower design
●User-friendly and easy-to-move LCD display
●Wide input voltage range (110-300 VAC)
●Active input power factor correction 0.99
●50Hz/60Hz inverter mode
●Energy saving and environmental protection mode (ECO)
●Emergency power off function (EPO)
● Generator compatible
●Charger capacity extended to 4A for long-term models
●SNMP/USB/RS-232 communication
3-level scalable charging design to optimize battery performance
●Isolation transformer can be provided
Product Specifications
MODEL | Galleon X9 6K(L) | Galleon X9 ISO 6K(L) | Galleon X9 10K(L) | Galleon X9 ISO 10K(L) | |
capacity | 6000 VA / 5400 W | 10000 VA / 9000 W | |||
phase | Single phase with ground | ||||
ENTER | |||||
voltage range | 110-300 VAC at 50% load; 176 -300 VAC at 100% load | ||||
Rated voltage | 200/208/220/230/240 VAC | ||||
Frequency Range | 46~54 Hz or 56~64 Hz | ||||
power factor | ≧ 0.99 @ 100% load | ||||
OUTPUT | |||||
AC voltage regulation | ± 1% | ± 3% | ± 1% | ± 3% | |
Frequency Range (Battery Mode) | 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz | ||||
Rated voltage | 200/208/220/230/240 VAC | 104 VAC x 2 / 208 VAC or 110 VAC x 2 / 220 VAC or 115 VAC x 2 / 230 VAC or 120 VAC x 2 / 240 VAC | 200/208/220/230/240 VAC | 104 VAC x 2 / 208 VAC or 110 VAC x 2 / 220 VAC or 115 VAC x 2 / 230 VAC or 120 VAC x 2 / 240 VAC | |
Current crest ratio | 3:1 (max.) | ||||
Harmonic Distortion | ≦ 2% THD (Linear Load); ≦ 4% THD (Non-linear Load) | ≦ 3.5% THD (Linear Load); ≦ 7% THD (Non-linear Load) | ≦ 2% THD (Linear Load); ≦ 4% THD (Non-linear Load) | ≦ 3.5% THD (Linear Load); ≦ 7% THD (Non-linear Load) | |
Frequency range (sync range) | 46~54 Hz or 56~64 Hz | ||||
CONVERSION TIME | |||||
Battery mode is line mode | Zero | ||||
bypass the inverter | Zero | ||||
Inverter Bypass | Zero | ||||
Line mode is battery mode | Zero | ||||
Waveform (Battery Mode) | Pure Sine Wave | ||||
EFFICIENCY | |||||
battery mode | 88% | 82% | 88% | 82% | |
ECO mode | 96% | 87% | 96% | 87% | |
Communication mode | 91% | 85% | 91% | 85% | |
BATTERY | |||||
long extension machine | Charge current (max) | 4A | |||
long extension machine | float voltage | 273 VDC (based on battery numbers at 20 pcs) | |||
long extension machine | Battery type and quantity | Depending on applications | |||
Standard machine | Charge current (max) | 1A | |||
Standard machine | Typical charging time | 7 hours recover to 90% capacity | 9 hours recover to 90% capacity | ||
Standard machine | number | 20 (18-20 pcs adjustable) | |||
Standard machine | float voltage | 273 VDC (based on battery numbers at 20 pcs) | |||
Standard machine | Battery Type | 12 V / 7 AH | 12 V / 9 AH | ||
INDEX | |||||
LCD panel | UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions | ||||
ALARM | |||||
battery mode | Sounding every 4 seconds | ||||
low power | Sounding every second | ||||
overload | Sounding twice every second | ||||
Fault | Continuously sounding | ||||
SURROUNDINGS | |||||
Working humidity | 0~95% RH @ 0- 40°C (non-condensing) | ||||
noise level | Less than 58dB @ 1 Meter | Less than 60dB @ 1 Meter | |||
PHYSICS | |||||
Standard machine | Net weight/kg | UPS unit: 20; Battery pack: 58 | UPS unit: 20; Battery pack: 58/ ISO bank: 61 | UPS unit: 23.5; Battery pack: 65 | UPS unit: 23.5; Battery pack: 65 ; ISO bank: 90 |
Standard machine | Dimensions, D X W X H (mm) | UPS unit: 606 x 438 x 133 [3U]; Battery pack: 606X438 X133 [3U] | UPS unit: 606 x 438 x 133 [3U]; Battery pack: 606X438 X133 [3U]; ISO bank: 606 x 438 x 133 [3U] | UPS unit: 686 x 438 x 133 [3U]; Battery pack: 606 x 438 x 133 [3U] | UPS unit: 686 x 438 x 133 [3U]; Battery pack: 606 x 438 x 133 [3U]; ISO bank: 686 x 438 x 133 [3U] |
long extension machine | Net weight/kg | 20 | UPS unit: 20; ISO bank: 61 | 23.5 | UPS unit: 23.5; ISO bank: 90 |
long extension machine | Dimensions, D X W X H (mm) | 606 x 438 x 133 [3U] | UPS unit: 606 x 438 x 133 [3U]; ISO bank: 606 x 438 x 133 [3U] | 686 x 438 x 133 [3U] | UPS unit: 606 x 438 x 133 [3U]; ISO bank: 606 x 438 x 133 [3U] |
MANAGE | |||||
Optional SNMP | Power management from SNMP manager and web browser | ||||
Smart RS-232/USB | Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7/8/10, Linux, and MAC |