产品概述:The LCD display panel is easy to operate and adjust the viewing angle direction. Ideal for medium power density power protection needs, the Galleon X9 series is···
The LCD display panel is easy to operate and adjust the viewing angle direction
Ideal for medium power density power protection needs, the Galleon X9 series is available in rack/tower form factors to suit a variety of environments. It has a small footprint, but the UPS has a built-in battery pack and can be accessed through the front panel for maintenance inspection and replacement, eliminating the need to remove the UPS from the rack mount. The LCD viewing angle can be easily adjusted by pressing a button on the LCD to correspond to rack or tower installations. In addition, IT staff can get the remaining battery backup time through the LCD display, so as to manage the equipment well.
main feature
●Real double conversion online UPS system
●Output power factor 0.9
●LCD display panel is easy to operate and adjust the viewing angle direction
●Rack and tower design
●Adjustable power management socket
●50/60Hz frequency conversion mode
●ECO energy saving operation function
●Emergency power off function (EPO)
●Hot-pull design, only for 1-3K models
●DSP technology is suitable for 6K and above models
●Active power factor correction is suitable for 6K and above models
●N+X parallel redundancy application is limited to 6K and above models
product description
MODEL | Galleon X9 II 1K | Galleon X9 II 1.5K | Galleon X9 II 2K | Galleon X9 II 3K | |
capacity | 1000 VA / 900 W | 1500 VA / 1350 W | 2000 VA / 1800 W | 3000 VA / 2700 W | |
phase | Single phase with ground | ||||
ENTER | |||||
voltage range | 55-150 VAC ± 5 % or 110-300 VAC ± 5 % at 50% load; 80-150 VAC ± 5 % or 160-300 VAC ± 5 % at 100% load | ||||
Rated voltage | 100*/110*/115*/120/127 VAC or 200/208/220/230/240 VAC | ||||
Frequency Range | 40Hz~70Hz | ||||
power factor | ≧ 0.99 @ Nominal Voltage (100% load) | ||||
Harmonic Distortion (THDi) | ≦ 5% @ nominal input voltage | ||||
OUTPUT | |||||
The output voltage | 100*/110*/115*/120/127 VAC or 200/208/220/230/240 VAC | ||||
AC Voltage Regulation (Voltage Mode) | ± 1% | ||||
Frequency Range (Battery Mode) | 50 Hz or 60 Hz ± 0.1 Hz | ||||
transfer time | Zero | ||||
Waveform (Battery Mode) | Pure Sine Wave | ||||
Current crest ratio | 3:1 (max.) | ||||
Harmonic Distortion | ≦ 2% THD (Linear Load); ≦ 4% THD (Non-linear load) | ||||
Frequency range (sync range) | 57~63 Hz or 47~53 Hz or | ||||
EFFICIENCY | |||||
battery mode | 88%, 89% | 89% | 88%, 89% | 90% | |
ECO mode | 97% | ||||
Communication mode | 90% | 91% | |||
BATTERY | |||||
long extension machine | Charger voltage | 27.4 VDC ± 1%, 41.1 VDC ± 1% | 41.1 VDC ± 1% | 54.8 VDC ± 1%, 82.1 VDC ± 1% | 82.1 VDC ± 1% |
long extension machine | Charge current (max) | 1A / 2A / 4A / 8A | |||
long extension machine | number | 2,3 | 3 | 4, 6 | 6 |
long extension machine | Battery Type | Depending on the capacity of external batteries | |||
Standard machine | Charger voltage | 27.4 VDC ± 1%, 41.1 VDC ± 1% | 41.1 VDC ± 1% | 54.8 VDC ± 1%, 82.1 VDC ± 1% | 82.1 VDC ± 1% |
Standard machine | Charge current (max) | 1.5 A | |||
Standard machine | Typical charging time | 4 hours recover to 90% capacity | |||
Standard machine | number | twenty three | 3 | 4, 6 | 6 |
Standard machine | Battery Type | 12 V / 9 AH, 12 V / 7 AH | 12 V / 9 AH | 12 V / 9 AH, 12 V / 7 AH | 12 V / 9 AH |
INDEX | |||||
LCD Monitor | Load level, Battery level, AC mode, Battery mode, Bypass mode, and Fault indicators | ||||
ALARM | |||||
battery mode | Sounding every 5 seconds | ||||
low power | Sounding every 2 seconds | ||||
overload | Sounding every second | ||||
Fault | Continuously sounding | ||||
SURROUNDINGS | |||||
Working humidity | 20~90% RH @ 0- 40°C (non-condensing) | ||||
noise level | Less than 50dB @ 1 Meter | ||||
PHYSICS | |||||
Standard machine | Net weight/kg | 11.6, 14.2 | 14.5 | 19.5, 26.9 | 27.4, 10.5 |
Standard machine | Dimensions, D X W X H (mm) | 410 x 438 x 88 [2U] | 510 x 438 x 88 [2U], 630 x 438 x 88 [2U] | 630 x 438 x 88 [2U] | |
long extension machine | Net weight/kg | 6.4 | 6.5 | 10.5 | |
long extension machine | Dimensions, D X W X H (mm) | 410 x 438 x 88 | 510 x 438 x 88 | ||
MANAGE | |||||
Optional SNMP | Power management from SNMP manager and web browser | ||||
Smart RS-232/USB | Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7/8/10, Linux, and MAC |