DR series 30~480 rail power supply

DR series 30~480 rail power supply

产品概述:Technical reference: Project technical indicators Output DC voltage 5V12V15V24V Rated current 3A2A2A1.5A Rated power 15W24W30W36W Ripple and noise ①<80mV<120mV<···

产品简介

Technical reference:

projectTechnical indicators
outputDC voltage 5V12V15V24V
Rated current3A2A2A1.5A
rated power15W24W30W36W
Ripple and Noise①<80mV<120mV<120mV<150mV
Voltage accuracy±2%±1%
Output voltage regulation range ±10% 
Load Regulation ±1% 
Linear adjustment rate ±1% 
entervoltage range85-264VAC 47Hz~63Hz (120VDC~370VDC)
Efficiency (Typical) ②>78%>82%>84%>84%
Working current<0.8A 110VAC <0.4A 220VAC
electric shock110VAC 15A, 220VAC 30A
Start, rise, hold time100ms, 30ms, 21ms: 110VAC/100ms, 30ms, 100ms: 220VAC
ProtectOverload protection     105%-150% Type: Protection Mode: Hiccup Mode Automatic recovery after abnormal condition is removed
Short circuit protection +VO drops to the undervoltage point and turns off the output Automatic recovery after the abnormal condition is removed
surroundingsWorking temperature and humidity-10℃~+50℃; 20%~90RH
Storage temperature and humidity-20℃~+85℃; 10%~95RH
SafetyWithstand voltage Input-Output: 3KVAC for 1 minute                                     
Isolation resistanceInput-Output, Input-Case, Output-Case: 500VDC/100MΩ
othersize78*93*56mm
Net weight/gross weight270/290g
Remark

①Ripple and noise measurement method: use a 12" twisted pair cable, and the terminals should be connected in parallel with 0.1uF and 47uF capacitors, and measure at 20MHz bandwidth

②The efficiency is tested under the input voltage of 230VAC, the rated load, and the ambient temperature of 25℃. 

Accuracy: including setting error, linear adjustment rate and load adjustment rate. 

Linear Regulation Test Method: Test from Low Voltage to High Voltage at Rated Load  

Load regulation test method: from 0%-100% rated load.

The start-up time is measured in the cold start state. Rapid and frequent switching of the machine may increase the start-up time. When the operating altitude is higher than 2000 meters, the operating environment temperature needs to be lowered by 5°C/1000 meters.

projectTechnical indicators
outputDC voltage  5V12V15V24V
Rated current5A3.5A2.8A2A
rated power25W42W42W48W
Ripple and Noise①<80mV<120mV<120mV<150mV
Voltage accuracy±2%±1%
Output voltage regulation range ±10% 
Load Regulation ±1% 
Linear adjustment rate ±1% 
entervoltage range85-264VAC 47Hz~63Hz (120VDC~370VDC)
Efficiency (Typical) ②>78%>82%>84%>84%
Working current<1A 110VAC <0.5A 220VAC
electric shock110VAC 15A, 220VAC 30A
Start, rise, hold time100ms, 30ms, 21ms: 110VAC/100ms, 30ms, 100ms: 220VAC
ProtectOverload protection     105%-150% Type: Protection Mode: Hiccup Mode Automatic recovery after abnormal condition is removed
Short circuit protection +VO drops to the undervoltage point and turns off the output Automatic recovery after the abnormal condition is removed
surroundingsWorking temperature and humidity-10℃~+50℃; 20%~90RH
Storage temperature and humidity-20℃~+85℃; 10%~95RH
SafetyWithstand voltage Input-Output: 3KVAC for 1 minute                                     
Isolation resistanceInput-Output, Input-Case, Output-Case: 500VDC/100MΩ
othersize78*93*56mm
Net weight/gross weight270/290g
Remark

①Ripple and noise measurement method: use a 12" twisted pair cable, and the terminals should be connected in parallel with 0.1uF and 47uF capacitors, and measure at 20MHz bandwidth

②The efficiency is tested under the input voltage of 230VAC, the rated load, and the ambient temperature of 25℃.

Accuracy: including setting error, linear adjustment rate and load adjustment rate.

Linear Regulation Test Method: Test from Low Voltage to High Voltage at Rated Load

Load regulation test method: from 0%-100% rated load.

The start-up time is measured in the cold start state. Rapid and frequent switching of the machine may increase the start-up time. When the operating altitude is higher than 2000 meters, the operating environment temperature needs to be lowered by 5°C/1000 meters.

projectTechnical indicators
outputDC voltage5V12V15V24V
Rated current6.5A4.5A4A2.5A
rated power32.5W54W60W60W
Ripple and Noise①<80mV<120mV<120mV<150mV
Voltage accuracy±2%±1%
Output voltage regulation range ±10% 
Load Regulation ±1% 
Linear adjustment rate ±1% 
entervoltage range85-264VAC 47Hz~63Hz (120VDC~370VDC)
Efficiency (Typical) ②>78%>82%>84%>84%
Working current<1.2A 110VAC <0.8A 220VAC
electric shock110VAC 15A, 220VAC 30A
Start, rise, hold time100ms, 30ms, 21ms: 110VAC/100ms, 30ms, 100ms: 220VAC
ProtectOverload protection     105%-150% Type: Protection Mode: Hiccup Mode Automatic recovery after abnormal condition is removed
Short circuit protection +VO drops to the undervoltage point and turns off the output Automatic recovery after the abnormal condition is removed
surroundingsWorking temperature and humidity-10℃~+50℃; 20%~90RH
Storage temperature and humidity-20℃~+85℃; 10%~95RH
SafetyWithstand voltage Input-Output: 3KVAC for 1 minute                                     
Isolation resistanceInput-Output, Input-Case, Output-Case: 500VDC/100MΩ
othersize78*93*56mm
Net weight/gross weight270/290g
Remark

①Ripple and noise measurement method: use a 12" twisted pair cable, and the terminals should be connected in parallel with 0.1uF and 47uF capacitors, and measure at 20MHz bandwidth.

②The efficiency is tested under the input voltage of 230VAC, the rated load, and the ambient temperature of 25℃.   

Accuracy: including setting error, linear adjustment rate and load adjustment rate.

Linear Regulation Test Method: Test from Low Voltage to High Voltage at Rated Load

Load regulation test method: from 0%-100% rated load.

The start-up time is measured in the cold start state. Rapid and frequent switching of the machine may increase the start-up time. When the operating altitude is higher than 2000 meters, the operating environment temperature needs to be lowered by 5°C/1000 meters.

projectTechnical indicators
outputDC voltage12V24V48V
Rated current6.3A3.2A1.6A
rated power76W76.8W76.8W
Ripple and Noise①<120mV<150mV<240mV
Voltage accuracy±2%±1%
Output voltage regulation range ±10% 
Load Regulation ±1% 
Linear adjustment rate ±0.5% 
entervoltage range85-264VAC 47Hz~63Hz (120VDC~370VDC)
Efficiency (Typical) ②>86%>88%>90%
Working current<1.6A 110VAC <0.96A 220VAC
electric shock110VAC 20A, 220VAC 40A
Start, rise, hold time1800ms, 60ms, 12ms: 110VAC/1000ms, 60ms, 60ms: 220VAC
ProtectOverload protection     105%-150% Type: Protection Mode: Hiccup Mode Automatic recovery after abnormal condition is removed
Short circuit protection +VO drops to the undervoltage point and turns off the output Automatic recovery after the abnormal condition is removed
surroundingsWorking temperature and humidity-10℃~+50℃; 20%~90RH    
Storage temperature and humidity-20℃~+85℃; 10%~95RH    
SafetyWithstand voltage Input-Output: 3KVAC Input-Ground: 1.5KVAC Output-Ground: 0.5KVAC for 1 minute                                     
leakage current<1mA/240VAC
Isolation resistanceInput-Output, Input-Case, Output-Case: 500VDC/100MΩ
othersize55.5*125.2*100mm
Net weight/gross weight600/650g
Remark

①Ripple and noise measurement method: use a 12" twisted pair cable, and the terminals should be connected in parallel with 0.1uF and 47uF capacitors, and measure at 20MHz bandwidth

②The efficiency is tested under the input voltage of 230VAC, the rated load, and the ambient temperature of 25℃.  

Accuracy: including setting error, linear adjustment rate and load adjustment rate. 

Linear Regulation Test Method: Test from Low Voltage to High Voltage at Rated Load

Load regulation test method: from 0%-100% rated load.

The start-up time is measured in the cold start state. Rapid and frequent switching of the machine may increase the start-up time. When the operating altitude is higher than 2000 meters, the operating environment temperature needs to be lowered by 5°C/1000 meters.

projectTechnical indicators
outputDC voltage24V48V
Rated current20A10A
rated power480W480W
Ripple and Noise①<120mV<240mV
Voltage accuracy±1%±1%
Output voltage regulation range ±10% 
Load Regulation ±1% 
Linear adjustment rate ±0.5% 
entervoltage range180-264VAC 47Hz~63Hz (270VDC~370VDC)
Efficiency (Typical) ②>84%>86%
Working current<2.5A 110VAC <1.3A 220VAC
electric shock110VAC 20A, 220VAC 35A
Start, rise, hold time3000ms, 100ms, 22ms: 110VAC/1500ms, 100ms, 28ms: 220VAC
ProtectOverload protection     105%-150% Type: Protection Mode: Hiccup Mode Automatic recovery after abnormal condition is removed
Overvoltage protectionWhen the output voltage is greater than 135%, the output is turned off. Automatic recovery after the abnormal condition is removed
Short circuit protection +VO drops to the undervoltage point and turns off the output. After the abnormal condition is removed, it will resume automatically after the power is restarted.
Over temperature protectionWhen >85°, the output will be turned off. After the temperature has dropped, it will be restored after the power is restarted.
surroundingsWorking temperature and humidity-10℃~+50℃; 20%~90RH
Storage temperature and humidity-20℃~+85℃; 10%~95RH
SafetyWithstand voltage Input-Output: 3KVAC Input-Ground: 1.5KVAC Output-Ground: 0.5KVAC for 1 minute                                     
leakage current<1.5mA/240VAC
Isolation resistanceInput-Output, Input-Case, Output-Case: 500VDC/100MΩ
othersize125.5*100*125.2mm
Net weight/gross weight1200/1230g
Remark

①Ripple and noise measurement method: use a 12" twisted pair cable, and the terminals should be connected in parallel with 0.1uF and 47uF capacitors, and measure at 20MHz bandwidth.

②The efficiency is tested under the input voltage of 230VAC, the rated load, and the ambient temperature of 25℃. 

Accuracy: including setting error, linear adjustment rate and load adjustment rate. 

Linear Regulation Test Method: Test from Low Voltage to High Voltage at Rated Load

Load regulation test method: from 0%-100% rated load.

The start-up time is measured in the cold start state. Rapid and frequent switching of the machine may increase the start-up time. When the operating altitude is higher than 2000 meters, the operating environment temperature needs to be lowered by 5°C/1000 meters.