产品概述:The highest power density three-phase modular online UPSAPlus is a modular online UPS that provides high efficiency value in a compact footprint and flexible an···
The Highest Power Density Three-Phase Modular On-Line UPS
APlus is a modular online UPS that provides high efficiency value in a compact footprint and flexible and scalable architecture, reaching 600kW using only 10 modules. The hot-swappable modular design and built-in maintenance bypass switch allow the system to be upgraded or serviced without disrupting mission-critical loads.
main feature
●3U 60KW single power supply module
●N+1 or N+X parallel redundancy to ensure uninterrupted power
●Support 1+1 cabinet parallel horizontal expansion
●Hot-plug modular design reduces MTTR
●High scalability
●Built-in maintenance bypass switch, easy maintenance without interruption
●Efficient double conversion online UPS
●Flexible battery configuration and adjustable charging current
●High overload capacity
●Power step-in function
●Built-in dynamic password protection
●Built-in super communication slot
Product Specifications
MODEL | A+ 30U-120 | A+ 30U-180 | A+ 42U-300 | A+ 42U-420 | A+ 42U-500 | A+ 42U-600 | |
Cabinet capacity | 120KW | 180KW | 300KW | 420KW | 500KW | 600KW | |
phase | 3-phase in/3-phase out | ||||||
Battery Type | 60KVA/60KW | ||||||
One power module capacity | 2 | 3 | 5 | 7 | 8 | 10 | |
ENTER | |||||||
voltage range | -30% ~ +20% | ||||||
Rated voltage | 3 x 380/400/415VAC (3Ph+N) | ||||||
Frequency Range | 40Hz ~70Hz | ||||||
power factor | > 0.99 at 100% load, >0.98 at 50% load | ||||||
Harmonic Distortion (THDi) | < 3% @ 100% load | ||||||
OUTPUT | |||||||
Rated frequency | 50/60Hz | ||||||
Voltage regulation (steady state) | ≦± 1% Typical (balanced load) ; ≦± 2% Typical (unbalanced load) | ||||||
Rated voltage | 3 x 380/400/415VAC (3Ph+N) | ||||||
efficiency | 0.96 | ||||||
Harmonic Distortion | ≦1% THD (Linear Load) ; ≦3% THD (Non-linear Load) | ||||||
Frequency range (sync range) | 46Hz ~ 54Hz or 56Hz ~ 64Hz | 46Hz ~ 54Hz or 56Hz ~ 64Hz | |||||
overload capacity | 1 hour for ≦ 110%, 10 mins for 111% ~ 125%, 1 min for 126%~150% and 200ms for >150% | ||||||
BATTERIES AND CHARGERS | |||||||
float voltage | 2.28V / Cell (2.25 ~2.33 Selectable) | ||||||
maximum voltage | +/- 240V (12V x 40 Pcs) | ||||||
Temperature compensation | Yes | ||||||
standard | +/- 192V ~ +/- 240V (Selectable) | ||||||
Minimum voltage | +/- 192V (12V x 32 Pcs) | ||||||
Equalizing voltage | 2.35V/Cell | ||||||
Maximum charging current (per power module) | 18A (Adjustable) | ||||||
SURROUNDINGS | |||||||
Operating temperature | 0 ~ 40℃ | ||||||
altitude | <1000m for Nominal power | ||||||
IP protection class | IP 20 | ||||||
Relative humidity | 0 ~ 95% non-condensing | ||||||
Net weight (kg) | 308 | 352 | 516 | 654 | 932 | 1020 | |
PHYSICS | |||||||
Cabinet Dimensions (DxWxH) mm | 1100 x 600 x 1475 | 1100 x 600 x 2010 | 1100 x 1200 x 2000 | ||||
STANDARD | |||||||
safety | IEC/EN 62040-1 | ||||||
Electromagnetic Compatibility | IEC/EN 62040-2 Category C3 | ||||||
POWER MANAGEMENT SYSTEM | |||||||
Optional SNMP | Power management from SNMP manager and web browser | ||||||
RS-232/USB | Supports Windows family, Linux and MAC |