产品概述:The parallel redundant design can be expanded to 10 parallel Arenas The patented modular design enhances the flexibility of power expansion and maintenance. The···
Parallel redundancy design can be expanded to 10 units in parallel
Arena's patented modular design enhances flexibility for power expansion and maintenance. The power module can be easily removed from the enclosure by simply removing the four screws on the connector box without disconnecting any wiring. Without the need for an additional cabinet chassis, Arena can be installed with servers in the same cabinet. In addition, the vertical/horizontal conversion design enhances the flexibility and choice of modular UPS. Compared with the general parallel system, Arena UPSs can form a power backup system by sharing the battery pack, which can greatly reduce the cost and achieve the same performance.
main feature
●N+1 or N+R1 parallel redundant application design increases system flexibility, stability and security
●Real double conversion online UPS system
●Modular junction box, hot-swappable design, easy capacity expansion, installation and maintenance
●Independent rack
●Battery can be shared in parallel mode
●The number of battery cells is adjustable
●DSP technology ensures high performance
●Output power factor 1.0
●50/60Hz frequency conversion mode
●ECO energy saving operation function
●Emergency power off function (EPO)
●Compatible with engine input
●Customized system
Product Specifications
MODEL | Arena 3/3-10K | Arena 3/1-10K | Arena 1/1-10K | Arena 2/2-6K LV | Arena 3/3-10K LV | |
capacity | 10000VA / 10000W | 10001VA / 10000W | 6000VA / 6000W | 10000VA / 8000W | ||
phase | 3 phase in / 3 phase out | 3 phase in / 1 phase out | 1 phase in / 1 phase out | 2 phase in / 2 phase out | 3 phase in / 3 phase out | |
Parallel capability | 10 | |||||
ENTER | ||||||
voltage range | 190-520 VAC (3-phase) @ 50% load; 305-478 VAC (3-phase) @ 100% load | 110-300 VAC @ 50% load; 176-276 VAC @ 100% load | 88-155VAC (LN); 152-269VAC (LL) | |||
Rated voltage | 3x360VAC / 380VAC / 400VAC / 415VAC (3Ph+N+PE) | 208VAC / 220VAC / 230VAC / 240VAC (1Ph+N+PE) | 100/200, 110/220, 120/208, 120/240, 127/220 VAC (2P+N+PE) | 3x173VAC / 190VAC / 200VAC / 208 / 220VAC (3Ph+N+PE) | ||
Frequency Range | 40~70Hz | |||||
power factor | ≧ 0.99 @ 100% load | |||||
Harmonic Distortion (THDi) | < 4% @ full linear load | |||||
OUTPUT | ||||||
The output voltage | 360VAC / 380VAC / 400VAC / 415VAC (3Ph+N) | 208/220/230/240VAC(L+N) | 100/200, 110/220, 120/208, 120/240, 127/220 VAC (2P+N) | 173VAC / 190VAC / 200VAC / 208 / 220VAC (3Ph+N) | ||
AC Voltage Regulation (Voltage Mode) | ± 1% | |||||
Frequency Range (Battery Mode) | 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz | |||||
transfer time | AC mode is battery mode | zero | ||||
transfer time | Inverter to Bypass | zero | ||||
Waveform (Battery Mode) | Pure Sine Wave | |||||
Current crest ratio | 3:1 (max.) | |||||
Harmonic Distortion | ≦ 2% THD (Linear Load); ≦ 3% THD (Non-linear Load) | |||||
Frequency range (sync range) | 46~54Hz or 56~64Hz | |||||
EFFICIENCY | ||||||
battery mode | Peak | 93.5% | 93% | 92.5% | 91.5% | 92.0% |
battery mode | fully loaded | 93% | 92.5% | 92% | 91% | 92% |
ECO mode | 97% | |||||
Communication mode | 94% | 93.5% | 91% | 92% | ||
BATTERIES AND CHARGERS | ||||||
Charging voltage | ±218V | ±109V | ||||
Typical charging time | 9 hours recover to 90% capacity | |||||
recharging current | +/- 4A | |||||
maximum voltage | +/- 240V (12V x 40pcs) | +/- 120V (12V x 20pcs) | ||||
Rated voltage | +/- 192V (12V x 32 Pcs) | +/- 96V (12V x 16pcs) | ||||
battery number | 16~20pcs (adjustable) x 2 | 8~10pcs (adjustable) x 2 | ||||
battery voltage | ± 12V / 9 Ah | |||||
Minimum voltage | +/- 192V (12V x 32 Pcs) | +/- 96V (12V x 16pcs) | ||||
INDEX | ||||||
LCD/LED display | UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions | |||||
SURROUNDINGS | ||||||
Working humidity | 0~95% RH @ 0- 40°C (non-condensing) | |||||
noise level | Less than 55dB @ 1 Meter | Less than 58dB @ 1 Meter | ||||
PHYSICS | ||||||
Dimensions, D X W X H (mm) | 678 X 418 X 132 [3U] | |||||
Net weight (kg) | 20.5 | 17.6 | twenty one | |||
MANAGE | ||||||
Optional SNMP | Power management from SNMP manager and web browser | |||||
Smart USB | Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7/8, Linux and MAC |