Galleon II 3P/3P RT 10K-60K

Galleon II 3P/3P RT 10K-60K

产品概述:PF 1.0 High Frequency UPS The Galleon II 33 Rack/Tower High Frequency UPS delivers an excellent output power factor of 1.0 for higher performance and efficiency···

产品简介

PF 1.0 High Frequency UPS

The Galleon II 33 Rack/Tower High Frequency UPS delivers an excellent output power factor of 1.0, delivering higher performance and efficiency for critical applications. And up to three units can be paralleled to provide an affordable solution for your mission-critical loads. Equipped with an adjustable current charger (up to 18A) to make your energy planning more flexible.

main feature

●Real double conversion online UPS system

●Auto-rotate LCD screen with rack-mounting orientation (only for 10K-30K models)

●DSP technology ensures high performance

●Output power factor 1

●All phases have active power factor correction

●50Hz/60Hz frequency conversion method

●ECO Energy Saving Mode Operation (ECO)

●Emergency power off function (EPO)

● Generator compatible

●Support dual AC input

3-level scalable charging design to optimize battery performance

●Adjustable number of batteries for long-running models

● Parallel operation with shared battery

●Optional isolation transformer provides complete isolation and complete common mode noise rejection

Product Specifications

MODELGalleon II 3P/3P Rack Tower 10K (L)Galleon II 3P/3P Rack Tower 15K (L)Galleon II 3P/3P Rack Tower 20K (L)Galleon II 3P/3P Rack Tower 30K (L)Galleon II 3P/3P Rack Tower 40K (L)Galleon II 3P/3P Rack Tower 60K (L)
capacity10KVA /10KW15KVA /15KW20KVA /20KW30KVA/30KW40KVA/40KW60KVA/60KW
phase3-phase in / 3-phase out
Parallel capability4
ENTER
voltage range190-520 VAC (3-phase) @50% load ; 305-478 VAC (3-phase)@ 100% load
Rated voltage3 x 400 VAC (3Ph+N) or 208*/220/230/240 VAC (Ph-N)
Frequency Range46 Hz~54 Hz or 56~64Hz
power factor≧ 0.99 @ 100% load
OUTPUT
The output voltage3 x 360*/380/400/415 VAC (3Ph+N) or 208*/220/230/240 VAC (Ph-N)
3 x 360*/380/400/415 VAC (3Ph+N)
Frequency Range (Battery Mode)± 1%
transfer timeAC mode is battery mode50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz
transfer timeInverter to BypassZero
Current crest ratioZero
Harmonic DistortionPure Sine Wave
Frequency range (sync range)3:1 (max.)
overloadCommunication mode≦ 2% THD (Linear Load); ≦ 5% THD (Non-linear Load)
overloadbattery mode46~54 Hz or 56~64 Hz
AC Voltage Regulation (Battery Mode)100- 110% for 60 min, 110- 125% for 10 min, 125%~150% for 1 min; >150% immediately
Waveform (Battery Mode)100- 110% for 60 min, 110- 125% for 10 min, 125%~150% for 1 min; >150% immediately
EFFICIENCY
battery mode94.5%0.945
ECO mode98.5%0.985
Communication mode95.50.955
BATTERY
Maximum charging currentDepending on the applications
Battery Type+/-13.65VDC ± 10+/-13.65V*N (N=16~20)
Charging voltage1A~12A (Adjustable)1A ~ 16A (Adjustable)1A ~ 18A (Adjustable)
Number of batteries (adjustable)20 pcs (Adjustable)32-40 pcs (Adjustable)
SURROUNDINGS
Operating temperature0- 40°C
Working humidity< 95% and non-condensing
noise levelLess than 62dB @ 1 MeterLess than 65dB @ 1 MeterLess than 70dB @ 1 Meter
PHYSICS
Dimensions, DxWxH(mm)680 X 438 X 133 (3U)797 X 438 X 176 (4U)
Net weight/kg2628294045
MANAGE
Optional SNMPPower management from SNMP manager and web browser
Smart RS-232/USBSupports Windows® family, Linux and MAC


Excel Energy Co., Ltd.

0577-62789660