产品概述:PF 1.0 High Frequency UPS The Galleon II 33 Rack/Tower High Frequency UPS delivers an excellent output power factor of 1.0 for higher performance and efficiency···
PF 1.0 High Frequency UPS
The Galleon II 33 Rack/Tower High Frequency UPS delivers an excellent output power factor of 1.0, delivering higher performance and efficiency for critical applications. And up to three units can be paralleled to provide an affordable solution for your mission-critical loads. Equipped with an adjustable current charger (up to 18A) to make your energy planning more flexible.
main feature
●Real double conversion online UPS system
●Auto-rotate LCD screen with rack-mounting orientation (only for 10K-30K models)
●DSP technology ensures high performance
●Output power factor 1
●All phases have active power factor correction
●50Hz/60Hz frequency conversion method
●ECO Energy Saving Mode Operation (ECO)
●Emergency power off function (EPO)
● Generator compatible
●Support dual AC input
3-level scalable charging design to optimize battery performance
●Adjustable number of batteries for long-running models
● Parallel operation with shared battery
●Optional isolation transformer provides complete isolation and complete common mode noise rejection
Product Specifications
MODEL | Galleon II 3P/3P Rack Tower 10K (L) | Galleon II 3P/3P Rack Tower 15K (L) | Galleon II 3P/3P Rack Tower 20K (L) | Galleon II 3P/3P Rack Tower 30K (L) | Galleon II 3P/3P Rack Tower 40K (L) | Galleon II 3P/3P Rack Tower 60K (L) | |
capacity | 10KVA /10KW | 15KVA /15KW | 20KVA /20KW | 30KVA/30KW | 40KVA/40KW | 60KVA/60KW | |
phase | 3-phase in / 3-phase out | ||||||
Parallel capability | 4 | ||||||
ENTER | |||||||
voltage range | 190-520 VAC (3-phase) @50% load ; 305-478 VAC (3-phase)@ 100% load | ||||||
Rated voltage | 3 x 400 VAC (3Ph+N) or 208*/220/230/240 VAC (Ph-N) | ||||||
Frequency Range | 46 Hz~54 Hz or 56~64Hz | ||||||
power factor | ≧ 0.99 @ 100% load | ||||||
OUTPUT | |||||||
The output voltage | 3 x 360*/380/400/415 VAC (3Ph+N) or 208*/220/230/240 VAC (Ph-N) | 3 x 360*/380/400/415 VAC (3Ph+N) | |||||
Frequency Range (Battery Mode) | ± 1% | ||||||
transfer time | AC mode is battery mode | 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz | |||||
transfer time | Inverter to Bypass | Zero | |||||
Current crest ratio | Zero | ||||||
Harmonic Distortion | Pure Sine Wave | ||||||
Frequency range (sync range) | 3:1 (max.) | ||||||
overload | Communication mode | ≦ 2% THD (Linear Load); ≦ 5% THD (Non-linear Load) | |||||
overload | battery mode | 46~54 Hz or 56~64 Hz | |||||
AC Voltage Regulation (Battery Mode) | 100- 110% for 60 min, 110- 125% for 10 min, 125%~150% for 1 min; >150% immediately | ||||||
Waveform (Battery Mode) | 100- 110% for 60 min, 110- 125% for 10 min, 125%~150% for 1 min; >150% immediately | ||||||
EFFICIENCY | |||||||
battery mode | 94.5% | 0.945 | |||||
ECO mode | 98.5% | 0.985 | |||||
Communication mode | 95.5 | 0.955 | |||||
BATTERY | |||||||
Maximum charging current | Depending on the applications | ||||||
Battery Type | +/-13.65VDC ± 10 | +/-13.65V*N (N=16~20) | |||||
Charging voltage | 1A~12A (Adjustable) | 1A ~ 16A (Adjustable) | 1A ~ 18A (Adjustable) | ||||
Number of batteries (adjustable) | 20 pcs (Adjustable) | 32-40 pcs (Adjustable) | |||||
SURROUNDINGS | |||||||
Operating temperature | 0- 40°C | ||||||
Working humidity | < 95% and non-condensing | ||||||
noise level | Less than 62dB @ 1 Meter | Less than 65dB @ 1 Meter | Less than 70dB @ 1 Meter | ||||
PHYSICS | |||||||
Dimensions, DxWxH(mm) | 680 X 438 X 133 (3U) | 797 X 438 X 176 (4U) | |||||
Net weight/kg | 26 | 28 | 29 | 40 | 45 | ||
MANAGE | |||||||
Optional SNMP | Power management from SNMP manager and web browser | ||||||
Smart RS-232/USB | Supports Windows® family, Linux and MAC |