产品概述:The PF0.9 High Power Density UPS Galleon Pro is the high power density version of the Galleon series with an output power factor of 0.9. From 10KVA to 30KVA, it···
PF0.9 high power density UPS
Galleon Pro is the high power density version of the Galleon series with an output power factor of 0.9. From 10KVA to 30KVA, it is designed with DSP technology and active input power factor correction to ensure better output voltage conditions, power quality and performance at all times. Its dual power input will ensure the reliability of the power supply.
main feature
●Real double conversion online UPS system
●DSP technology ensures high performance
●Output power factor 0.9
●The input power factor can reach 0.99
●50/60Hz frequency conversion mode
●ECO energy saving operation function
● Compatible with dual input
●Emergency power off function (EPO)
●Compatible with engine input
●Multiple communication ports such as SNMP/USB/RS-232
●3-section intelligent charging design
●The number of battery cells is adjustable
●Built-in maintenance bypass switch
●Optional N+X parallel redundant application design increases flexibility
●Wide input voltage range (110-300 VAC)
●Built-in phase adaptation function simplifies wiring installation
●Adjustable power management socket
MODEL | Galleon Pro 3/1-10K (L) | Galleon Pro 3/1-15K (L) | Galleon Pro 3/1-20K (L) | Galleon Pro 3/1-30K (L) | |
capacity | 10000 VA / 9000 W | 15000 VA / 13500 W | 20000 VA / 18000 W | 30000 VA / 27000 W | |
phase | 3 phase in / 1 phase out | ||||
ENTER | |||||
voltage range | 190-520 VAC (3-phase) @ 50% load; 305-478 VAC (3-phase) @ 100% load | ||||
Rated voltage | 3 x 400 VAC (3Ph+N) | ||||
Frequency Range | 46~54 Hz or 56~64Hz | ||||
power factor | ≧ 0.99 @ 100% load | ||||
OUTPUT | |||||
The output voltage | 1 x 400 VAC (1Ph+N) | ||||
AC Voltage Regulation (Voltage Mode) | ± 1% | ||||
Frequency Range (Battery Mode) | 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz | ||||
Waveform (Battery Mode) | Pure Sine Wave | ||||
Current crest ratio | 3:1 (max.) | ||||
Harmonic Distortion | ≦ 2% THD (Linear Load); ≦ 5% THD (Non-linear Load) | ||||
Frequency range (sync range) | 46~54Hz or 56~64Hz | ||||
AC mode is battery mode | zero | ||||
Inverter Bypass | zero | ||||
EFFICIENCY | |||||
battery mode | 87.0% | 88.0% | 89.0% | ||
ECO mode | 96.0% | ||||
Communication mode | 90.5% | 91.5% | 92.1% | ||
BATTERY | |||||
long extension machine | Charger voltage | 273 VDC ± 1% | |||
long extension machine | Charge current (max) | 4A | 12A | ||
long extension machine | number | Depending on the capacity of external batteries | |||
long extension machine | Battery Type | Depending on the capacity of external batteries | |||
Standard machine | Charger voltage | 273 VDC ± 1% | |||
Standard machine | Charge current (max) | 1A | 2A | 4A | |
Standard machine | Typical charging time | 9 hours recover to 90% capacity | |||
Standard machine | quantity | 20 pcs (18-20 pcs adjustable) | 20 pcs (18-20 pcs adjustable) x 2 strings | 20 pcs (18-20 pcs adjustable) x 3 strings | |
Standard machine | Battery Type | 12 V / 9 AH | |||
INDEX | |||||
LCD panel | UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions | ||||
ALARM | |||||
battery mode | Sounding every 4 seconds | ||||
low power | Sounding every second | ||||
overload | Sounding twice every second | ||||
Fault | Continuously sounding | ||||
SURROUNDINGS | |||||
Working humidity | 0~95% RH @ 0- 40°C (non-condensing) | ||||
noise level | Less than 60dB @ 1 Meter | Less than 65dB @ 1 Meter | |||
PHYSICS | |||||
Standard machine | Net weight/kg | 109 | 164 | 233.5 | |
Standard machine | Dimensions, D X W X H (mm) | 815 x 250 x 826 | 815 x 300 x 1000 | ||
long extension machine | Net weight/kg | 38 | 40 | 64 | |
long extension machine | Dimensions, D X W X H (mm) | 592 x 250 x 826 | 592 X 250 X 826 | 815 x 250 x 826 | |
MANAGE | |||||
Optional SNMP | Power management from SNMP manager and web browser | ||||
Smart RS-232/USB | Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7/8/10, Linux, and MAC |